Dashboard

SITE-001 · THAI TRADITIONAL MEDICINE HOSPITAL (J4012)
STATE: NORMAL_GRID
LIVE STREAM
AGE: 0.2s
DSP: 2.81 ms
Attention Required Automatic Connected 4 alarm (1 crit)
Synced 14:28
DAILY ENERGY
112.00 kWh
Revenue ฿392.00
↗ 4.7% ↗ 5.1%
MONTHLY ENERGY
3,409.28 kWh
Revenue ฿11,932.48
↗ 8.2% ↗ 9.3%
TOTAL ENERGY
17,384.10 kWh
Revenue ฿60,844.35
↗ 12.4% ↗ 11.8%
CARBON CREDIT
8.69 tCO₂e
Est. Value ฿869.20
↗ 10.5% ↗ 6.8%
กริด
↓ 8%
24.0 kW
IMPORT
Today 91.8 kWh
Total load 218.0 kWh
EXPORT
Today 0.0 kWh
Solar produced 112.0 kWh
BATTERY
↑ 2%
0.0 kW
SOC 85%
CHARGE
from Grid 5.9 kWh
from PV 17.8 kWh
DISCHARGE
to Normal Load 10.8 kWh
to Critical Load 2.7 kWh
SOLAR
↑ 14%
18.5 kW
DAILY
Solar produced 112.0 kWh
Today 112.0 kWh
NON-GRID SUPPLY
Today 112.0 kWh
Export 0.0 kWh
LOAD
↑ 4%
42.5 kW
CRITICAL LOAD
Today 97.8 kWh
Crit 24.5 kW
NORMAL LOAD
Today 120.2 kWh
Norm 18.0 kW
Single-Line Power Flow Topology (SLD) · Site-001 Hospital Microgrid
PEA Grid Solar PV / DVR PCS Hospital Loads
24.0 kW 18.0 kW 6.0 kW 6.0 kW 18.5 kW 24.5 kW PEA GRID (JANITZA) 24.0 kW PF 0.980 · THD 1.4% DVR-PLUS 30kVA STANDBY STS Closed · <2.8ms Sag CRITICAL LOAD 24.5 kW Fl.1 ICU/OR · PM2230 NORMAL LOAD 18.0 kW Fl.4 Wards · PM2230 BESS EBC 768V 85.0% 768.2 V · 0.0 A · 29.5°C SOLAR PV (HUAWEI) 18.5 kW SUN2000-30KTL · 164.5 kWh
Phase Electrical Parameters TRUE RMS
Phase Voltage (V) Current (A) THD-V (%) Status
Phase A 381.2 36.5 1.82 Normal
Phase B 380.5 35.8 1.79 Normal
Phase C 381.8 36.9 1.85 Normal
Annunciator Alarms
Time Severity Event State
12:40:12 INFO BMS Modbus RTU ID:1 heartbeat valid (COM1 9600 bps) HEALTHY
12:15:30 INFO DVR-PLUS 30 kVA PCS fast-wake armed (<2.8 ms) HOT READY
11:58:02 INFO PEA Incomer Janitza sync confirmed (380V / 50.02 Hz) NOMINAL

Energy Flow

24-hour overview · stacked power contributions
โซล่าร์
แบตเตอรี่
ไฟจากกริด
โหลดรวม
SoC แบตเตอรี่
Digital Storage Oscilloscope: 3-Phase Bus Waveforms
RUNNING
Timebase:
Volt Scale:
Channels:
Trigger: LINE LOCK · 50.00 Hz
RMS: 402.5 V
V_PP: 569.2 V
SAMPLE RATE: 40 kSPS
COUPLING: AC/DC DIRECT
Grid Frequency
50.02 Hz
Sync Lock: ±0.02 Hz
Reactive Power
15.2 kVAr
Inductive Cancellation Active
Apparent Load
256.1 kVA
Capacity Factor: 85.3%
Neutral Current
1.2 A
Balanced Load Network
Voltage THD (Total)
1.8 %
Limit: < 3.0 % (IEEE 519)
Current THD (Total)
3.2 %
Limit: < 5.0 %
Voltage Unbalance
0.78 %
IEC 61000 Limit: < 2.0 %
Harmonic Filter
ACTIVE
DSP Real-time Cancellation
Harmonic Order Spectrum Analysis (Fundamental 50 Hz to 25th Harmonic) FFT WINDOW: 10 CYCLES
LiFePO4 High-Voltage Battery Bank (EBC 768V · Site-001) BMS ONLINE · COM1
85.0 % SOC
Nameplate Capacity: 61.44 kWh (20 Mod.)
Pack DC Voltage: 768.2 V
Current Flow: 0.0 A (Float)
Cell ΔV Imbalance: 12 mV (<300mV)
Max Cell Voltage: 3.205 V (Mod. 14)
Min Cell Voltage: 3.193 V (Mod. 08)
Pack Temperature: 29.5 °C (<55°C)
State of Health (SOH): 99.5 %
Fieldbus Protocol: RS-485 Modbus ID: 1
Baudrate & Format: 9600 bps 8N1
BESS EBC Modbus RTU Sequential Registers COM1 · SLAVE ID 1
Address Parameter Description Raw Telemetry Diagnostic Status
Reg 38 Pack Terminal Voltage (0.1V) 768.2 V Normal Range
Reg 39 Pack Battery Current (0.1A) 0.0 A Float Standby
Reg 40 State of Charge - SOC (0.1%) 85.0 % Optimal
Reg 41 State of Health - SOH (0.1%) 99.5 % Healthy
Reg 35 Maximum Cell Voltage 3.205 V Balanced
Reg 36 Minimum Cell Voltage 3.193 V Balanced
Reg 37 Maximum Cell Temperature 29.5 °C Optimal Cooling
Reg 132-139 Protection Alarm Bitfields 0x0000 Zero Alarms
ANSI / IEEE C37 Hardware Protection Matrix COORDINATED SETPOINTS
ANSI Code Protection Function Trip Setpoint Response Delay Arm Status
59 Overvoltage Protection 110.0 % (440 V) < 10 ms Armed
27 Undervoltage Protection 85.0 % (340 V) < 10 ms Armed
50/51 Instantaneous Overcurrent 120.0 % (360 A) < 1 ms Armed
81O/U Under / Over Frequency 47.5 - 52.5 Hz < 100 ms Armed
49 Thermal Overload Inverter Sink > 85.0 °C < 500 ms Armed
COM1: BESS EBC 768V BMS
POLLING OK
9600 bps 8N1 · Slave ID: 1 · /dev/ttyUSB0
COM2: DVR-PLUS PCS 30kVA
POLLING OK
19200 bps 8N1 · Slave ID: 2 · /dev/ttyUSB1
COM3: PM2230 Fl.4 (Normal)
POLLING OK
9600 bps 8N1 · Slave ID: 6 · /dev/ttyUSB2
COM4: PM2230 Fl.1 (ICU/OR)
POLLING OK
19200 bps 8E1 · Slave ID: 8 · /dev/ttyUSB3
Modbus TCP: SmartLogger2000
CONNECTED
192.168.6.200:502 · Huawei PV / Janitza / Weather
Edge Gateway: Seeed J4012
HEALTHY
Jetson Orin Nano 8GB · Python 3.14 · 6-Cores
PCS MODE:STANDBY
DC BUS:750.2 Vdc
ACTIVE POWER:0.0 kW
DC CURRENT:0.0 A
BESS SOC:85.0 %
IGBT TEMP:42.4 °C
PWM GATES:READY (FAST-WAKE)
PCS Operational Mode & Setpoints (Bi-Directional Converter) DVR-PLUS RMS 30 kVA (COM2 ID: 2)
Select active operational profile for the Bi-Directional Power Conversion System (PCS). All setpoint modifications write directly to DSP control registers with ISA-101 dual-stage verification.
STANDBY
HOT READY
DC Link pre-charged at 768 Vdc (LiFePO4 EBC 20S rack). PWM gate pulses inhibited to eliminate switching losses. Sub-cycle fast-wake auto-ignition (<2.8 ms) upon grid sag event.
CHARGE
AC → DC
Rectifier operation: draws regulated power from AC bus / PV to charge LiFePO4 battery pack with programmable power, current limits, and zero-export buffer protection.
DISCHARGE
DC → AC
Inverter operation: injects power into facility bus for load peak-shaving (>45 kW), series sag boost assistance (<2.8 ms), or scheduled dispatch with deep-discharge protection.
Standby Operational Parameters & Fast-Wake Readiness
Precharge Contactor State
CLOSED / 768V BUS ENERGIZED
Idle Standby Inverter Loss
0.14 kW (Control & Auxiliary)
Battery Charge Parameters (AC → DC Rectifier Mode)
Battery Discharge Parameters (DC → AC Inverter Mode)
PEA Incomer & Microgrid Dispatch Limits JANITZA UMG 96RM
Site-001 Microgrid Dispatch Logic EMS MASTER ACTIVE
• P_grid = P_load (PM2230 Fl1+Fl4) - P_solar (Huawei) - P_pcs
• If P_grid > 45.0 kW: State → PEAK_SHAVING (Discharge 15 kW)
• If P_grid < 3.0 kW: State → ZERO_EXPORT (Charge 10 kW / Derate)
• Sub-cycle sag detection <2.8 ms triggers series boost
High-Precision Sequence of Events (SOE Audit Log) RESOLUTION: 1.0 ms
Timestamp (UTC) Tag ID Event Category Before After Operator / Source
2026-09-15 05:14:22.180 SETPOINT_VREF Config Modification 398 V 400 V Station Admin
2026-09-15 03:42:01.050 RELAY_TRIP_CLR Fault Clearance SAG_ALERT NORMAL DSP Autoreclose
2026-09-15 00:00:00.000 BESS_DAILY_DIAG Diagnostics FLOAT FLOAT BMS Routine
Subsystem Asset Maintenance Ledger
Subsystem Asset Last Inspection Next Scheduled Overhaul Interval Health Index Condition
LiFePO4 EBC 768V Battery Rack (20S) 2026-07-15 2026-10-15 90 Days SOH 99.5% Normal
DVR-PLUS 30 kVA PCS Forced Air Cooling 2026-08-01 2026-11-01 90 Days Airflow Nominal Normal
reComputer J4012 Edge Gateway & Python EMS 2026-08-10 2026-11-10 90 Days Temp 38.2°C Normal
Janitza UMG 96RM & STS Transfer Switch 2026-05-20 2027-05-20 365 Days Calibrated Normal